Surge Protection for Process Systems (Telematic)
While the importance of surge protection for industrial and process plant has been
appreciated for many years, the rapid development of computerized control, monitoring, and
security systems has made it even more imperative for modern process systems which
recognize that any externally-cabled connections are possible sources of potentially
damaging surges. Complete protection can only be provided by protecting all cable routes
into plant structures.


The figure illustrates a typical industrial process layout and highlights those areas
which are most at risk from lightning and surge damage. In areas that are most likely to
pass induced currents into sensitive or critical equipment, surge protection should be
considered essential.
The threat
to process systems
Most process control or telemetry installations are interconnected by power and signal
cables which run on trays, in ducting or via overhead poles. Lightning strikes, static
discharges and induction from power cabling are typical sources of transient voltages
which can be coupled into signal cables and hence transmitted to electronic equipment.
Field transmitters, computer terminals, etc, containing low-power semiconductor devices
can be damaged by over voltages of only tens of volts. The longer the cables, the more
frequent the occurrence of high voltage transients through shifts in ground potential, so
devices controlling or monitoring events in remote locations are more likely to suffer
from over voltages and consequent component failures. Significant damage can also be found
in equipment connected by relatively short cables if the circuits or components are
particularly sensitive - as is the case for computer data communication ports.


As an illustration, consider the effects of a lightning strike to a building, housing
control and telemetry equipment, of which the fabric is protected from a direct strike by
a lightning conductors and ground rods as shown in the figure above. The conductor carries
the very large strike current into the earth termination and dissipates the charge
transfer into the mass of the earth. The effect of this current is to elevate the
reference potential at the building. For example, if the strike current is 100kA and the
conductor/ground impedance, is 10 ohms, then the potential above ground is 1 million
volts. Exposed metalwork within the building is bonded to the same reference potential and
so only small voltage differences exists, posing little risk to personnel.

The field transmitter is pole-mounted away from the control building but connected to the
telemetry electronics by signal cabling. Most transmitters incorporate some level of
isolation from structural earth, typically 500V. This level of isolation now has to
withstand the transient voltage between the new building reference potential and its local
earth potential. Many transmitters are destroyed in this way, even though the actual
lightning strike was to a protected building.
Loop protection
For complete protection, it is usually necessary to protect both ends of a loop, as any
surge protection device can only provide local protection. SPDs control voltage and divert
surge currents relative to their local earth points and therefore remote devices need
their own individual protection. However, in average industrial plants many individual
items of remote field instrumentation are relatively inexpensive and easy to replace, the
cost of loop failure is not great, and the risk of damage from local surge currents is
slight. Therefore, in these circumstances, it may be thought desirable to confine
protection to the control room end of the loop where much more vital control equipment
affecting the whole process (or a major part of it) may be at risk.

However, there are some areas of application where field instrumentation should be
protected. These include loops which are vital to the process, field devices which are
inherently expensive (such as some types of transmitters), and loops in which the field
instrumentation is located in very remote or inaccessible locations. Major users of SPDs
for remote field instrumentation include the utility companies which maintain what are
often far-flung distribution and monitoring systems. For these companies it is both
inconvenient and expensive to send an engineer many miles to replace fuses or failed
sensors, so it is economically good sense for them to provide remote instrumentation with
modern maintenance-free and auto-resetting SPDs.

Telematic supply some unique SPDs designed specifically for use with particular items of
field instrumentation . These devices incorporate proven hybrid surge protection circuits
and are designed for mounting within or on the instrumentation for which they are
specified. Some specific applications for advanced surge protection technology from
Telematic is discussed below.
SPDs for process transmitter systems
SPDs are a valuable safeguard in loops based on process variable transmitters (ie, either
conventional or 'smart,' 4 to 20mA, 2-wire transmitters for flow, temperature, pressure,
level). It is assumed that the transmitter is driven from a bulk dc power supply and
terminates in a 250 ohm load resistor as part of an instrument or a control system input
card. Other types of process transmitter loop can be treated in a similar fashion with
small adjustments to loop voltage drops.

Transmitters are often supplied by the manufactures with optional built-in 'protection,'
generally a clamping diode network that, while it certainly reduces transmitter failure,
can only handle relatively low-power surges. Heavy surges (of the type likely to be caused
by a nearby lightning strike) will almost certainly destroy both the protection circuit
and the transmitter. Higher levels of protection - particularly for remotely located
transmitters - are therefore worth considering to avoid downtime losses and the
considerable cost of replacing equipment at some distance from the centre of operations.



The figure above illustrates a typical loop configuration with an SPD located at the
control room end of the loop only. The working voltage of the selected SPD must be higher
than the supply voltage to prevent unacceptable errors being caused by leakage currents
through the SPD diodes. The usual power supply arrangement is a bulk dc supply with a
common negative providing the system 0V reference. This supply is normally a nominal +24V,
so a 32V working voltage SPD is suitable. A suitable SPD is Telematics SD32 which is
provided with a 250mA replaceable fuse and a disconnect feature which is desirable for
most applications. An equivalent SPD without the replaceable fuse option is the SD32X (the
fuse is not necessary for correct SPD operation). Including an SPD means that the power
supply minimum output voltage must be capable of tolerating the additional voltage drop
incurred by the SPD impedance. The line resistances of Telematics SD32 and SD32X
SPDs are negligible (4 and 2 ohms respectively) so, for all practical purposes can be
ignored.
Field SPDs
for process transmitters
SPDs are not necessarily needed for transmitters when the loop is within a covered plant.
However, if the transmitter variable is particularly vital to the process or if it is
remote and unprotected by any surrounding steelwork, then protection is advisable.
Transmitters on tall structures such as distillation columns are also vulnerable to high
voltages between the case and the circuitry caused by lightning currents flowing down the
structure, as also are transmitters located close to structural steelwork used as
lightning conductors, an increasingly common practice. The transmitter illustrated in the
Figure below would be subject to a voltage stress of more than 100kV between its case and
the internal electronics. Any or all these factors must be taken into account when
deciding if protection is desirable.

SPDs fitted to transmitters should attempt to provide a preferential break-down path
between lines and lines-earth so that any surge currents thus induced flow along that path
rather than through the transmitter circuitry. The type of transient protection offered as
an optional extra by most transmitter manufacturers generally consists of surge
suppression diodes or, occasionally, varistors. The former type provides protection only
against low-voltage and the latter only against high-voltage surges. Devices incorporating
hybrid circuits combining gas discharge tubes varistors and surge suppression diodes are
the obvious answer but, until relatively recently, were not easy to implement on account
of the physical difficulties of packaging the more complex network within the body of the
transmitter.

The better solution is to use a 'dedicated' external SPD, designed specifically for easy
and convenient use with transmitters, such as Telematics TP48 device. This is a
small unit which is mounted by screwing it into a spare 'cable entry' on the transmitter
casing as shown in the figure below. Three flying leads are provided for connection to
line 1, line 2 and earth as shown. It is available both in a standard version and also in
two 'explosion-protection' versions (ie, intrinsically-safe and flameproof). All versions
are available with a variety of screw-threads to suit virtually all currently available
transmitters and can be retrofitted to existing installations without affecting loop
wiring or performance. TP48 SPDs provide protection against ALL surges up to 10kA and
achieve 60V differential mode protection, figures much better than those of the
transmitter manufacturers options.


Alternatively, a separate SPD such as one of the SD Series can be used but, if this is
done, it should be protected by a suitable weatherproof enclosure. If this latter option
is selected, then the field-mounted SPD must be locally bonded since it is the local
potential between the structure and the signal cables which needs to be controlled. The
SPD should therefore be bonded to the mounting bracket of the transmitter (if possible)
with a substantial and secure cable. Note that the TP48 is bonded directly to the
transmitter - an eminently satisfactory earthing solution, as you cant get much
closer than that!
SPDs for
comprehensive transmitter loop protection
When a transmitter or other field-mounted equipment is protected by an SPD then the
parallel paths created by the installation make it necessary also to protect the
control-room end of the loop. The majority of installations take the form of the circuit
shown in the figure below. The end-to-end resistance of the two suppression circuits is
very low (less than 10 ohms in total) and hence does not appreciably affect the circuit
operation. For example, with a 24V supply, a transmitter requiring a minimum of 12V and a
computer requiring 5V, the available voltage for line resistance and other accessories is
7V, which is more than adequate for most applications.



The circuit shown in the above figure illustrates the use of an SD32 SPD at the
control-room end to provide fuse protection to prevent a field short-circuit fault
affecting the operation of the rest of the circuit sharing the common power supply. The
circuit disconnect facility of the SD32 is useful for maintenance purposes. If this latter
facility is not needed, then an SD32X (which does not include the replaceable
fuse/disconnect link facility) can be used instead of the SD32.

The maximum supply voltage can be allowed to exceed 32V by a small margin since leakage
current from the power supply rail to the 0V of the system does not affect the measurement
accuracy. However, voltages in excess of 35V could blow the fuse. In a relatively small
number of applications it is necessary to increase the loop voltage for operational
reasons. This can be because of: extremely long land lines, additional equipment such as
indicators or trip amplifiers at the transmitter end of the loop, or control-room
equipment that needs a signal voltage of more than 5V.

In this case the Telematic SD55 can be deployed, to provide a maximum working voltage of
48V. If it is not necessary to be concerned about achieving a very low circuit current for
detecting an open circuit transmitter, then a voltage higher than 48V can be applied.
Operationally, the transmitter always consumes more than 4mA and the voltage drop created
by this current can be used to increase the supply volts. Generally however, it is usually
practical (and less complicated!) to use a supply voltage of 48V or less.
SPDs for
use with vibration sensors
The 3-wire transmitters used with vibration monitoring equipment are invariably supplied
by a 24V dc power supply, so the recommended Telematic SPD choice to protect the
control-room end of the loop is an SD32 or SD32X unit. Where the probe and its driver must
also be protected, then a suitable field-mounted SPD such as the Telematic mSA30/2 should
be used. Direct connection of the field wiring to ground at more than one point is not
recommended since the resulting circulating current will cause measurement problems. If it
is considered desirable to 'isolate' the system from earth and all three wires need
protecting then this can be done by using the 4-channel mSA30/2. Each channel has a
resistance of 43 ohms and hence the most effective result is achieved by paralleling two
channels and using them in the 0V line which is most affected by resistance.
SPDs for
temperature sensors
Sensors commonly used for temperature measurement are relatively simple devices such as
thermocouples (THCs) and resistance temperature detectors (RTDs). While these are hardly
immune to damage and destruction caused by high-voltage transients and surge currents, the
replacement cost is generally so low that protection for them in the field is rarely
provided unless they are difficult to replace or the particular temperature measured is so
vital to the process that the cost or consequences of any downtime makes the installation
of an SPD worthwhile. In the control-room however, the receiving and control equipment is
also liable to damage from surges and the replacement and downtime cost will almost
certainly be more than enough to warrant the installation of an SPD.

Signals from temperature sensors of the type described are usually of low voltage and the
end-to-end resistance of SPD channels is only significant for RTDs. Temperature
measurement with RTDs is resistance sensitive to the extent that 3- and 4-wire RTD
connections are used to eliminate the effects of lead resistance changes on the
measurement resistance change. RTDs in protected circuits must be either 2-wire types (ie,
RTDs which are not particularly inherently accurate and are therefore mainly suitable for
use as an over-temperature trip) or a 4-wire type in which a constant-current source is
used to compensate for variations in lead and SPD resistance. The working voltage selected
for an SPD to protect instrumentation connected to field temperature sensors is not
critical since the leakage specification voltage is likely to be orders of magnitude
greater than the system operating voltage.
SPDs for
temperature monitoring of large motors
Temperature monitoring of large motors is a case where SPDs should be specified to protect
panel instrumentation from power faults and transients on the motor windings. The figure
below illustrates a typical installation of this type in which a thermocouple is used for
temperature sensing. If the thermocouple is insulated, then the transient potential
between the thermocouple and the motor structure is determined by the current flowing
through the structure and other return paths. The potential is therefore the supply
voltage potentially divided between the return path impedance and the source impedance
plus the fault voltage. Hence the return path must be of low impedance or the voltage
developed can be high. With a 440V 3-phase motor, the 250V with respect to earth is likely
to have a transient voltage of 100V or so until the protective network operates. On higher
voltage motors, unless the fault current is restricted, the transient voltage is
correspondingly higher and further precautions such as installing an SPD as shown are
necessary to protect the instrumentation/monitoring circuits.



In general, Telematic SD07/SD07X SPDs are suitable for protecting THCs and RTDs in the
field and SD16/SD16X SPDs for protecting the related control-room instrumentation.
SPDs for
weighing installations
Weighbridges are frequently located in exposed conditions and the load cells associated
with them are therefore susceptible to lightning-induced surges and it is advisable to
protect both the 'field' load-cells as well as the associated control-room equipment.
Telematic provides specialist SPDs (the LC30 system) designed for mounting under
weigh-bridges and between silo legs and which are suitable for virtually all strain-gauge,
load-cell, weighbridge cabins, silos, and process storage facilities.

The system covers working voltages up to 30V and handles maximum surge currents of 10kA.
The LC30 system components and their applications are described in detail in Telematic
Application Note1006, Surge protection for weighing systems (available for free download
in the Departments area of this site).
SPDs for
miscellaneous low-voltage analogue circuits
Apart from temperature sensors, other low-voltage analogue loop field devices which may
need control-room and field protection include ac sensors, photocells, microphones and
turbine flowmeters. Suitable SPDs for these are the Telematic SD07 and SD16 units. For
slidewire displacement transducers, the recommended choices are usually the Telematic SD07
and SD07X.
SPDs for
protecting instrumentation systems
Incoming signal cabling to electronic systems is usually by twisted pairs or co-axial
lines. Because of the wide choice of applications, a variety of data transmission speeds
and system characteristics, there are a number of choices of SPDs based on fast hybrid
circuitry.

Apart from the near 'universal' DIN-mounting Telematic SD Series discussed elsewhere,
other suitable ranges include busbar-mounting units ( Telematic 375 range) Eurocard
19-inch rack mounting devices (Telematic DP Series) and backplane-mounting units for close
integration into DCSs (Telematic SP4300 Series). Most of these cover virtually the same
range of applications as the SD Series. Additionally, there is the Telematic CA range of
'in-line' co-axial SPDs which insert into co-axial lines with minimal insertion loss and
VSWR with wide bandwidth. The CA range is available with a wide choice of terminations to
suit virtually all applications (including panel-bulkhead fitting).
SPDs for
hazardous-area applications
Intrinsic safety is the most common and generally preferred technique of explosion
protection for measurement and control instrumentation in process hazardous areas, ie,
areas where a potentially explosive atmosphere may occur. Measurement Technology Limited
(a sister company of Telematic Limited in the MTL Instruments Group) is the worlds
leading supplier of intrinsically safe instrumentation and co-operates closely with
Telematic in the development of surge protection devices suitable for use in protecting
intrinsically safe circuits against lightning-induced transients or other high-power fault
surges.

The technique of intrinsic safety works basically by ensuring that under all circumstances
the amount of electrical power that can reach hazardous-area process equipment from
safe-area control equipment is limited to a maximum of approximately 1W. To make sure this
occurs, intrinsically safe (IS) interfaces are generally included in the control loop at
the safe-area end. IS interfaces are of two kinds, either shunt-diode (ie, Zener) safety
barriers or galvanic isolators. The former shunt fault currents to earth while the latter,
as the name suggest, 'isolate' fault currents. Safety barriers are less expensive but
isolators have the advantage that they can incorporate additional signal processing
circuits to provide a double function.

This brief introduction to surge protection in IS circuits has not touched on the various
IS certification requirements of national and international standards authorities which
can affect the implementation of surge protection in these circuits, nor the stringent
earthing requirements (except in the USA!) imposed upon surge protection systems. Those
with a particular interest in this application are advised to read Telematic Application
Note (TAN) 1004, Surge protection for intrinsically safe systems and also TAN1005, Surge
suppression for Zone 0 locations. All Telematic Application Notes are available for free
download in the Departments area of this web site.
SPDs for
telemetry systems
As the first providers of distributed cabled networks (much of it out-of-doors and
covering long distances) telephone systems were also one of the first major users of surge
protection devices, hence the application of surge protection to telemetry is widely
accepted and, generally, well understood.

Many telemetry systems use telephone lines (either private 'dedicated' or public dial-up)
for signal transmission and SPDs used for these applications must be approved by a PTT
(Post Telephone and Telegraph Organization) such as BT. Bearing in mind the openly
distributed nature of many telemetry installations, it is clearly advisable to protect
equipment at both ends of the line and Telematic has borne this in mind with the product
range available for these applications.

Telephone systems use fairly high dc voltages for line supply and bell operation. Typical
system working voltages are of the order of 40 to 50V dc. In the UK, ringing voltages are
120 to 140V but some systems can impose ringing voltages of up to 270V. Electronic
telecommunications equipment includes 'subscriber line interface circuits,' which have
voltage withstands of the order of 60V or so. SPDs used in public telephone systems
are frequently required to be approved by a national post, telephone and telegraph (PTT)
organization. In the U.K. this was the British Approvals Board for Telecommunications
(BABT) until the recent liberalization of the requirements.

Standard Zener or surge diodes with breakdown voltages of the order of 180V can provide
clamping of transient surges but the power dissipation in the component is high and leads
either to an unacceptably high cost or to a reduced life expectancy for the network. To
solve this problem, 'foldback' diodes have been designed which behave as conventional
Zener diodes below a critical voltage known as the voltage breakdown level or
VBR, i.e., a small amount of reverse leakage current. Above VBR, the device begins to
conduct very rapidly, the changeover taking place in picoseconds (10-12
seconds). With a conventional Zener diode, as voltage increases across it, current
increases through it with a slope resistance of typically 1 or 2 ohms. With foldback
diodes however, the voltage across the unit collapses to a much lower value when the
current is flowing through it, thereby significantly reducing the internal power
dissipation.

Specialist SPDs for telemetry applications include the DP200/4 SPD and the PX SPDs - both
of which are PTT approved. The former is designed for installation between line jacks and
telephone socket outlets to protect equipment such as fax machines, modems, extension
telephones, etc; while the latter units are designed to protect local PABX exchanges
against surges on incoming lines. All these units handle surge currents up to 10kA.
Assessing
protection requirements
In determining protection needs, it is necessary to balance the relative cost of providing
protection against the probability of damage and the costs and consequences of such
damage. Except in very exceptional circumstances, the possibility of a lightning strike
directly hitting electronic instrumentation is usually discounted. Extreme cases such as
wind gauges on the highest point of an offshore rig are an example of a conspicuous
exception. In such a case, the gauge itself is destroyed but the equipment connected to it
can be protected by suitable SPDs.
The risk of lightning-induced or other surges occurring on interconnecting
cables.
The cost of damage to equipment directly or indirectly connected to the cables.
This should include an assessment of the availability of spares and the accessibility of
the equipment should repairs be necessary.
The consequential cost of downtime caused before damage can be rectified, such as
loss of production or work in progress on a computer system.
The safety implications of damage. This factor is frequently difficult to assess
in purely financial terms if there is the possibility of human injuries or fatalities.
Thus, emergency shut-down (ESD) systems and fire alarm monitors are typical of the systems
which call for a high degree of protection for safety reasons.
Please see the -Building Systems- section of this web site for a discussion of surge
protection of systems found in process plant administration buildings, including power,
telephone, and computer systems.

SPDs fitted to transmitters should attempt to provide a preferential break-down path
between lines and lines-earth so that any surge currents thus induced flow along that path
rather than through the transmitter circuitry. The type of transient protection offered as
an optional extra by most transmitter manufacturers generally consists of surge
suppression diodes or, occasionally, varistors. The former type provides protection only
against low-voltage and the latter only against high-voltage surges. Devices incorporating
hybrid circuits combining gas discharge tubes varistors and surge suppression diodes are
the obvious answer but, until relatively recently, were not easy to implement on account
of the physical difficulties of packaging the more complex network within the body of the
transmitter.

The better solution is to use a 'dedicated' external SPD, designed specifically for easy
and convenient use with transmitters, such as Telematics TP48 device. This is a
small unit which is mounted by screwing it into a spare 'cable entry' on the transmitter
casing as shown in the figure below. Three flying leads are provided for connection to
line 1, line 2 and earth as shown. It is available both in a standard version and also in
two 'explosion-protection' versions (ie, intrinsically-safe and flameproof). All versions
are available with a variety of screw-threads to suit virtually all currently available
transmitters and can be retrofitted to existing installations without affecting loop
wiring or performance. TP48 SPDs provide protection against ALL surges up to 10kA and
achieve 60V differential mode protection, figures much better than those of the
transmitter manufacturers options.



Alternatively, a separate SPD such as one of the SD Series can be used but, if this is
done, it should be protected by a suitable weatherproof enclosure. If this latter option
is selected, then the field-mounted SPD must be locally bonded since it is the local
potential between the structure and the signal cables which needs to be controlled. The
SPD should therefore be bonded to the mounting bracket of the transmitter (if possible)
with a substantial and secure cable. Note that the TP48 is bonded directly to the
transmitter - an eminently satisfactory earthing solution, as you cant get much
closer than that!
SPDs
for comprehensive transmitter loop protection
When a
transmitter or other field-mounted equipment is protected by an SPD then the parallel
paths created by the installation make it necessary also to protect the control-room end
of the loop. The majority of installations take the form of the circuit shown in the
figure below. The end-to-end resistance of the two suppression circuits is very low (less
than 10 ohms in total) and hence does not appreciably affect the circuit operation. For
example, with a 24V supply, a transmitter requiring a minimum of 12V and a computer
requiring 5V, the available voltage for line resistance and other accessories is 7V, which
is more than adequate for most applications.




The circuit shown in the above figure illustrates the use of an SD32 SPD at the
control-room end to provide fuse protection to prevent a field short-circuit fault
affecting the operation of the rest of the circuit sharing the common power supply. The
circuit disconnect facility of the SD32 is useful for maintenance purposes. If this latter
facility is not needed, then an SD32X (which does not include the replaceable
fuse/disconnect link facility) can be used instead of the SD32.

The maximum supply voltage can be allowed to exceed 32V by a small margin since leakage
current from the power supply rail to the 0V of the system does not affect the measurement
accuracy. However, voltages in excess of 35V could blow the fuse. In a relatively small
number of applications it is necessary to increase the loop voltage for operational
reasons. This can be because of: extremely long land lines, additional equipment such as
indicators or trip amplifiers at the transmitter end of the loop, or control-room
equipment that needs a signal voltage of more than 5V.

In this case the Telematic SD55 can be deployed, to provide a maximum working voltage of
48V. If it is not necessary to be concerned about achieving a very low circuit current for
detecting an open circuit transmitter, then a voltage higher than 48V can be applied.
Operationally, the transmitter always consumes more than 4mA and the voltage drop created
by this current can be used to increase the supply volts. Generally however, it is usually
practical (and less complicated!) to use a supply voltage of 48V or less.
SPDs for
use with vibration sensors
The 3-wire transmitters used with vibration monitoring equipment are invariably supplied
by a 24V dc power supply, so the recommended Telematic SPD choice to protect the
control-room end of the loop is an SD32 or SD32X unit. Where the probe and its driver must
also be protected, then a suitable field-mounted SPD such as the Telematic mSA30/2 should
be used. Direct connection of the field wiring to ground at more than one point is not
recommended since the resulting circulating current will cause measurement problems. If it
is considered desirable to 'isolate' the system from earth and all three wires need
protecting then this can be done by using the 4-channel mSA30/2. Each channel has a
resistance of 43 ohms and hence the most effective result is achieved by paralleling two
channels and using them in the 0V line which is most affected by resistance.
SPDs for
temperature sensors
Sensors commonly used for temperature measurement are relatively simple devices such as
thermocouples (THCs) and resistance temperature detectors (RTDs). While these are hardly
immune to damage and destruction caused by high-voltage transients and surge currents, the
replacement cost is generally so low that protection for them in the field is rarely
provided unless they are difficult to replace or the particular temperature measured is so
vital to the process that the cost or consequences of any downtime makes the installation
of an SPD worthwhile. In the control-room however, the receiving and control equipment is
also liable to damage from surges and the replacement and downtime cost will almost
certainly be more than enough to warrant the installation of an SPD.

Signals from temperature sensors of the type described are usually of low voltage and the
end-to-end resistance of SPD channels is only significant for RTDs. Temperature
measurement with RTDs is resistance sensitive to the extent that 3- and 4-wire RTD
connections are used to eliminate the effects of lead resistance changes on the
measurement resistance change. RTDs in protected circuits must be either 2-wire types (ie,
RTDs which are not particularly inherently accurate and are therefore mainly suitable for
use as an over-temperature trip) or a 4-wire type in which a constant-current source is
used to compensate for variations in lead and SPD resistance. The working voltage selected
for an SPD to protect instrumentation connected to field temperature sensors is not
critical since the leakage specification voltage is likely to be orders of magnitude
greater than the system operating voltage.
SPDs for
temperature monitoring of large motors
Temperature monitoring of large motors is a case where SPDs should be specified to protect
panel instrumentation from power faults and transients on the motor windings. The figure
below illustrates a typical installation of this type in which a thermocouple is used for
temperature sensing. If the thermocouple is insulated, then the transient potential
between the thermocouple and the motor structure is determined by the current flowing
through the structure and other return paths. The potential is therefore the supply
voltage potentially divided between the return path impedance and the source impedance
plus the fault voltage. Hence the return path must be of low impedance or the voltage
developed can be high. With a 440V 3-phase motor, the 250V with respect to earth is likely
to have a transient voltage of 100V or so until the protective network operates. On higher
voltage motors, unless the fault current is restricted, the transient voltage is
correspondingly higher and further precautions such as installing an SPD as shown are
necessary to protect the instrumentation/monitoring circuits.



In general, Telematic SD07/SD07X SPDs are suitable for protecting THCs and RTDs in the
field and SD16/SD16X SPDs for protecting the related control-room instrumentation.
SPDs for
weighing installations
Weighbridges are
frequently located in exposed conditions and the load cells associated with them are
therefore susceptible to lightning-induced surges and it is advisable to protect both the
'field' load-cells as well as the associated control-room equipment. Telematic provides
specialist SPDs (the LC30 system) designed for mounting under weigh-bridges and between
silo legs and which are suitable for virtually all strain-gauge, load-cell, weighbridge
cabins, silos, and process storage facilities.

The system covers working voltages up to 30V and handles maximum surge currents of 10kA.
The LC30 system components and their applications are described in detail in Telematic
Application Note1006, Surge protection for weighing systems (available for free download
in the Departments area of this site).
SPDs for
miscellaneous low-voltage analogue circuits
Apart from temperature sensors, other low-voltage analogue loop field devices which may
need control-room and field protection include ac sensors, photocells, microphones and
turbine flowmeters. Suitable SPDs for these are the Telematic SD07 and SD16 units. For
slidewire displacement transducers, the recommended choices are usually the Telematic SD07
and SD07X.
SPDs for
protecting instrumentation systems
Incoming signal cabling to electronic systems is usually by twisted pairs or co-axial
lines. Because of the wide choice of applications, a variety of data transmission speeds
and system characteristics, there are a number of choices of SPDs based on fast hybrid
circuitry.

Apart from the near 'universal' DIN-mounting Telematic SD Series discussed elsewhere,
other suitable ranges include busbar-mounting units ( Telematic 375 range) Eurocard
19-inch rack mounting devices (Telematic DP Series) and backplane-mounting units for close
integration into DCSs (Telematic SP4300 Series). Most of these cover virtually the same
range of applications as the SD Series. Additionally, there is the Telematic CA range of
'in-line' co-axial SPDs which insert into co-axial lines with minimal insertion loss and
VSWR with wide bandwidth. The CA range is available with a wide choice of terminations to
suit virtually all applications (including panel-bulkhead fitting).
SPDs for
hazardous-area applications
Intrinsic safety is the most common and generally preferred technique of explosion
protection for measurement and control instrumentation in process hazardous areas, ie,
areas where a potentially explosive atmosphere may occur. Measurement Technology Limited
(a sister company of Telematic Limited in the MTL Instruments Group) is the worlds
leading supplier of intrinsically safe instrumentation and co-operates closely with
Telematic in the development of surge protection devices suitable for use in protecting
intrinsically safe circuits against lightning-induced transients or other high-power fault
surges.

The technique of intrinsic safety works basically by ensuring that under all circumstances
the amount of electrical power that can reach hazardous-area process equipment from
safe-area control equipment is limited to a maximum of approximately 1W. To make sure this
occurs, intrinsically safe (IS) interfaces are generally included in the control loop at
the safe-area end. IS interfaces are of two kinds, either shunt-diode (ie, Zener) safety
barriers or galvanic isolators. The former shunt fault currents to earth while the latter,
as the name suggest, 'isolate' fault currents. Safety barriers are less expensive but
isolators have the advantage that they can incorporate additional signal processing
circuits to provide a double function.

This brief introduction to surge protection in IS circuits has not touched on the various
IS certification requirements of national and international standards authorities which
can affect the implementation of surge protection in these circuits, nor the stringent
earthing requirements (except in the USA!) imposed upon surge protection systems. Those
with a particular interest in this application are advised to read Telematic Application
Note (TAN) 1004, Surge protection for intrinsically safe systems and also TAN1005, Surge
suppression for Zone 0 locations. All Telematic Application Notes are available for free
download in the Departments area of this web site.
SPDs for
telemetry systems
As the first providers of distributed cabled networks (much of it out-of-doors and
covering long distances) telephone systems were also one of the first major users of surge
protection devices, hence the application of surge protection to telemetry is widely
accepted and, generally, well understood.

Many telemetry systems use telephone lines (either private 'dedicated' or public dial-up)
for signal transmission and SPDs used for these applications must be approved by a PTT
(Post Telephone and Telegraph Organisation) such as BT. Bearing in mind the openly
distributed nature of many telemetry installations, it is clearly advisable to protect
equipment at both ends of the line and Telematic has borne this in mind with the product
range available for these applications.

Telephone systems use fairly high dc voltages for line supply and bell operation. Typical
system working voltages are of the order of 40 to 50V dc. In the UK, ringing voltages are
120 to 140V but some systems can impose ringing voltages of up to 270V. Electronic
telecommunications equipment includes 'subscriber line interface circuits,' which have
voltage withstands of the order of 60V or so. SPDs used in public telephone systems
are frequently required to be approved by a national post, telephone and telegraph (PTT)
organisation. In the U.K. this was the British Approvals Board for Telecommunications
(BABT) until the recent liberalisation of the requirements.

Standard Zener or surge diodes with breakdown voltages of the order of 180V can provide
clamping of transient surges but the power dissipation in the component is high and leads
either to an unacceptably high cost or to a reduced life expectancy for the network. To
solve this problem, 'foldback' diodes have been designed which behave as conventional
Zener diodes below a critical voltage known as the voltage breakdown level or
VBR, i.e., a small amount of reverse leakage current. Above VBR, the device begins to
conduct very rapidly, the changeover taking place in picoseconds (10-12
seconds). With a conventional Zener diode, as voltage increases across it, current
increases through it with a slope resistance of typically 1 or 2 ohms. With foldback
diodes however, the voltage across the unit collapses to a much lower value when the
current is flowing through it, thereby significantly reducing the internal power
dissipation.

Specialist SPDs for telemetry applications include the DP200/4 SPD and the PX SPDs - both
of which are PTT approved. The former is designed for installation between line jacks and
telephone socket outlets to protect equipment such as fax machines, modems, extension
telephones, etc; while the latter units are designed to protect local PABX exchanges
against surges on incoming lines. All these units handle surge currents up to 10kA.
Assessing
protection requirements
In determining protection needs, it is necessary to balance the relative cost of providing
protection against the probability of damage and the costs and consequences of such
damage. Except in very exceptional circumstances, the possibility of a lightning strike
directly hitting electronic instrumentation is usually discounted. Extreme cases such as
wind gauges on the highest point of an offshore rig are an example of a conspicuous
exception. In such a case, the gauge itself is destroyed but the equipment connected to it
can be protected by suitable SPDs. The principal assessment factors are:
The risk of lightning-induced or other surges occurring on interconnecting
cables.
The cost of damage to equipment directly or indirectly connected to the cables.
This should include an assessment of the availability of spares and the accessibility of
the equipment should repairs be necessary.
The consequential cost of downtime caused before damage can be rectified, such as
loss of production or work in progress on a computer system.
The safety implications of damage. This factor is frequently difficult to assess
in purely financial terms if there is the possibility of human injuries or fatalities.
Thus, emergency shut-down (ESD) systems and fire alarm monitors are typical of the systems
which call for a high degree of protection for safety reasons.
|